YBM22-12/0.4 outdoor pre-installed substation
YBM22-12/0.4 outdoor pre-installed substation
FOB
Shipping:
Ocean freight
Sample:Free supportGet samples
Product details
Essential details
Shipping:Ocean freight
Product Introduction

Product overview

YBM22 series pre-installed substation is a high-voltage electrical equipment, transformers, low-voltage electrical equipment combined into a compact complete set of power distribution devices, used in urban high-rise buildings, urban and rural buildings, residential areas, high-tech development zones, small and medium-sized factories, mines, oil fields and temporary construction electricity and other places, for the distribution system to receive and distribute electricity. The product has the characteristics of strong complete set, small size, compact structure, safe and reliable operation, convenient maintenance and movable. Compared with regular civil substations, the same capacity of box-type substations usually covers only 1/10~1/5 of regular substations, greatly reducing the design workload and construction volume, and reducing construction costs. In the power distribution system, it can be used in the ring network power distribution system, and can also be used in the dual power supply or radiation terminal power distribution system. It is a new complete set of equipment for the construction and transformation of urban and rural substations. YBM22 series prefabricated substation in line with GB/T17467-1998 "high voltage/low voltage prefabricated substation" national standard.

Model and meaning

 

Use of environmental conditions

Air temperature: upper limit ≤ 40 ℃, lower limit ≥-10 ℃;

◆ Solar radiation: ≤ 1000 W/m2;

◆ Altitude: ≤ 1000m;

◆ Icing: ≤ 20mm;

◆ Wind speed: ≤ 35 m/s;

◆ Humidity: daily average relative humidity <95%, monthly average relative humidity ≤ 90%, daily average relative water vapor pressure ≤ 2.2kPa, monthly average relative water vapor pressure ≤ 1.8kPa;

◆ Earthquake: ≤ 8 degrees;

◆ No fire, explosion hazard, serious pollution, chemical corrosion and severe vibration of the place.

Note: special conditions of use, when ordering proposed to negotiate with the manufacturer to resolve.

Main technical parameters

Main Technical Parameters
Serial NumberNameUnitHigh-voltage electrical equipmentTransformerLow-voltage electrical equipment
1Rated voltagekV1010/0.40.4
2Rated currentA630 100~2500
3Rated frequencyHz505050
4Rated capacitykVA 100~1250 
5Rated thermal stability currentkA20/4S 30/1S
6Rated dynamic stability current (peak value)kA50 63
7Rated closing short-circuit current (peak)kA50 15~30
8Rated breaking short-circuit currentkA31.5 (fuse)  
9Rated breaking load currentA630  
101min power frequency withstand voltagekVTo the ground, interphase 42 Interfracture 4835/28(5min)20/2.5
11Lightning impulse withstand voltagekVTo the ground, between 75 and 85.75 
12Protection class of shell IP23IP23IP23
13Noise leveldB Oil transformer 55, dry transformer 65 
14Number of loopsOne1~624~30
15Maximum reactive power compensation at low voltage sidekvar  300