Product overview
This unit is indoor metal-armored withdrawable switchgear, a complete power distribution unit of 3-10kV three-phase AC 50Hz single-bus segmented system.
It is mainly used in power plants, small and medium-sized generators, industrial and mining enterprises and distribution, as well as the secondary substation of electrical systems, power transmission and large high-voltage motor starting. The implementation of control protection, monitoring purposes. This switchgear meets the requirements of DL/T404-91, IEC298, GB3906 and other standards. It has interlocking functions of preventing closing of the combiner when the grounding switch is in the closed position, preventing accidental entry into the live compartment, and preventing accidental closing of the grounding switch when the grounding switch is charged. It can be equipped with both VS1 vacuum circuit breaker and VD4 vacuum circuit breaker of ABB Company. It is a kind of power distribution device with superior performance.
Use of environmental conditions
Normal environmental conditions:
◆ 1. Ambient air temperature:-10 ℃ ~ 40 ℃;
◆ 2. Altitude: not more than 1000m;
◆ 3. Relative environmental humidity: daily average is not more than 95%, monthly average is not more than 90%;
◆ 4, the surrounding air should not be corrosive or flammable gas, water vapor and other obvious pollution;
◆ 5. There is no serious pollution and frequent violent vibration, and the severity design meets the requirements of Class 1 under severe conditions.
Special working conditions:
◆ When used under normal environmental conditions exceeding GB3906, the user and the manufacturer shall negotiate.
Main structural features
This switchgear is designed for the armored metal-enclosed switchgear in the GB3906-91. The whole is composed of two parts: a cabinet body and a center-mounted extractable part (I. e. handcart). The cabinet body is divided into four separate compartments. The protection grade of the enclosure is IP4X. When each compartment and the circuit breaker door are opened, the protection grade is IP2X. It has air inlet and outlet lines, cable inlet and outlet lines and other functional schemes, which can become power distribution devices in various schemes after arrangement and combination.
The switch-on equipment can be installed, debugged and maintained from the front, so it can be arranged back-to-back and installed against the wall, which improves the safety and flexibility of the switchgear and reduces the floor area.
Main technical parameters
Main Technical Parameters of KYN28A-12 Indoor AC Metal Armored Mid-mounted Switchgear | |
Rated voltage (kV) | 3/6/10 |
Maximum operating voltage (kv) | 3.6/7.2/12 |
Power frequency withstand voltage (kv) | 42(1min) |
Impulse withstand voltage (kV) | 75 |
Rated frequency | 50Hz |
Rated current (A) | 630-3150 |
Rated thermal stability current (kA4s) | 16-50 |
Rated dynamic stability current (kA) | 40-125 |
Rated short-circuit breaking current (kA) | 16-50 |
Rated short-circuit opening and closing current (kA) | 40-125 |
Rated voltage of opening and closing and auxiliary circuit (V) DC | 24,30,48,60,110,220, AC 110,220 |
Protection level | IP4X |
VS1 and VD4 type vacuum circuit breaker skill parameter table | ||||
Project | Unit | VS1 | VD4 | |
Rated voltage | kV | 3 6 10 | ||
Maximum operating voltage | kV | 3.6 7.2 12 | ||
Rated insulation level | 1min power frequency withstand voltage | kV | 42 | |
Lightning impulse withstand voltage | kV | 75 | ||
Rated frequency | Hz | 50 | ||
Rated current | A | 630,1250,1600,2000,2500,3150 | ||
Rated short-circuit breaking current (effective value) | kA | 16,20,25,31.5,40,50 | ||
4S thermal stability current (effective value) | kA | 16,20,25,31.5,40,50 | ||
Rated dynamic stability current (peak value) | kA | 40,50,63,80,100,125 | ||
Transient recovery voltage rise rate | KV/ms | 0.345 0.415 | ||
Peak transient recovery voltage | kV | 20.6 30 | ||
Rated operating sequence | Points -0.3S-combined points -180S-combined points | |||
Automatic reclosing operation sequence | Points -0.3S-combined points -3min-combined points | |||
Multiple Reclosing Operation Sequence | Points -0.3S-combined points -15S-combined points -15S-combined points | |||
Closing time | ms | 100 | 70 | |
Opening time | ms | 20 | 45 | |
Arcing time | ms | 15 | 15 | |
Breaking time | ms | 65 | 60 |