Product overview
FLK-XF-110 type fire electrical control device (fire pump control equipment) according to the national standard GB16806-2006 "fire linkage control system" production and manufacturing, can meet the control requirements for fire water pump. It can automatically switch the open circuit and fault of the fire pump; it has the protection functions of phase loss, overload, overcurrent and short circuit for the starting of the motor; it has complete functions, flexible and reliable. The equipment can be used for fire water supply in various fields.
Specifications
The control cabinet adopts 380V/50Hz power supply, control pump power 110kW.
Model and meaning

Use of environmental conditions
◆ Ambient temperature: 0- 40 ℃
◆ Relative humidity: below 90% (electric control part)
◆ Surrounding environment: medium without explosion hazard, no corrosive metal and wet gas and dust that damage insulation
Working conditions
◆ Requirements according to the installation of electrical equipment technical standards and equipment capacity wiring
◆ The control cabinet should be well grounded, grounding resistance should be <0.1Ω
Structural features
◆ FLK-XF-110-type fire electrical control device (fire pump control equipment) adopts relay control mode, manual control is preferred, and the fire signal is automatically pumped during automatic control. The design is flexible and reliable.
Working principle
◆ 1, fire electrical control device (fire pump control equipment) is mainly used for fire hydrant system, generally using the star triangle start way. One control and two uses one for one standby.
◆ 2. The system has manual and automatic functions. When it is automatic, the white action indicator light will be on. When the fire signal arrives, a water pump will be automatically started. When it is manual, the manual indicator light will be on, and the water pump to be started can be manually started and stopped.
◆ 3. The system has failover function. When one pump is overloaded, the other pump will be put into operation, and the yellow fault indicator will light up and the buzzer will alarm.
◆ 4. The system has remote control and signal feedback interface, which can be connected to fire hydrant, fire center, etc. When the fire hydrant or fire center starts the DC24V fire signal, the fire hydrant control cabinet will automatically start the fire hydrant pump operation.
◆ 5. The system has the function of phase loss and phase error protection. When the phase loss and phase error signals arrive, the pump stops running and the buzzer alarms.
Technical characteristics
Star triangle start: for the power of 110kW pump can generally use the star triangle start way.
Dimensions, weight
Size and weight table | ||
Model | Dimensions (mm) | Weight (kg) |
FLK-XF-110 | 800 × 525 × 2000 | 180 |