FLK-FPY-30 type fire electrical control device (smoke control fan, dual power control equipment)
FLK-FPY-30 type fire electrical control device (smoke control fan, dual power control equipment)
FOB
Shipping:
Ocean freight
Sample:Free supportGet samples
Product details
Essential details
Shipping:Ocean freight
Product Introduction

Product overview

FLK-FPY-30 type fire electrical control device (smoke fan, dual power control equipment) according to the national standard GB16806-2006 "fire linkage control system" production and manufacturing, can meet the control requirements for fire smoke. It has the protection functions of phase loss, overload, overcurrent and short circuit for the starting of the motor; it has complete functions, flexible and reliable. The equipment can be used for smoke exhaust in various fields.

Specifications

The control cabinet adopts 380V/50Hz power supply, control fan power 30kW.

Model and meaning

Use of environmental conditions

◆ Ambient temperature: 0- 40 ℃

◆ Relative humidity: below 90% (electric control part)

◆ Surrounding environment: medium without explosion hazard, no corrosive metal and wet gas and dust that damage insulation

Working conditions

◆ Requirements according to the installation of electrical equipment technical standards and equipment capacity wiring

◆ The control cabinet should be well grounded, grounding resistance should be <0.1Ω

Structural features

◆ The FLK-FPY-30 fire electrical control device (smoke control fan, dual power control equipment) adopts relay control mode, manual control priority automatic control when the fire signal automatically starts, flexible and reliable design.

Working principle

◆ 1, fire electrical control device (smoke fan, dual power control equipment) is mainly used for fire smoke exhaust system, generally using direct start.

◆ 2. The system has manual and automatic functions. When it is automatic, the automatic indicator light is on. When the fire signal arrives, the fan will be automatically started; when it is manual, the manual indicator light is on and can be started and stopped manually.

◆ 3, the system has a remote control and signal feedback interface, can be connected to the fire center. When the fire center starts the DC24V fire signal, the smoke control and exhaust fan control cabinet will automatically start the fan operation.

◆ 4. The system has the function of phase loss and phase error protection. When the phase loss and phase error signals arrive, the fan stops running and the buzzer alarms.

Technical characteristics

Direct start: for the power of 30KW fan can generally use direct start way.

Dimensions, weight

Size and weight table
ModelDimensions (mm)Weight (kg)
FLK-FPY-30600 × 350 × 120080